-
Rated Capacity: 200 kVA / 180 kW
-
UPS Type / Topology: True Online Double-Conversion (transformerless)
-
Input Voltage (Nominal): 380 / 400 / 415 VAC (3-Phase + Neutral + Earth)
-
Input Voltage Range:
• 138-485 VAC at ~40% load
• 305-485 VAC at full load -
Input Power Factor: ≥ 0.99
-
Input Total Harmonic Distortion (THDi): ≤ 3% with linear loads
-
Bypass (Nominal) / Bypass Voltage Range: Configurable ±10%, ±15%, ±20%, ±25%
-
Output Voltage: 380 / 400 / 415 VAC (3Ph + N + PE)
-
Voltage Regulation: ±1%
-
Output Power Factor: 0.9
-
Crest Factor: 3:1
-
Output Voltage Distortion (THDv): ≤ 3% (for non-linear loads)
-
Overload Capability (Inverter Mode):
• ≤ 110% load → 60 minutes
• ≤ 125% load → 10 minutes
• ≤ 150% load → 1 minute -
Efficiency: ~ 96%
-
Transfer Time: 0 ms (seamless switching)
-
Battery Voltage Range: ±180 VDC to ±300 VDC
-
Charging Current: Up to ~ 60 A (adjustable)
-
Communication Interfaces: USB, RS-232, RS-485, dry contacts; intelligent slot; optional SNMP / relay cards
-
Remote Monitoring: Supported via remote LCD panel or external monitoring options
-
Operating Temperature: 0 °C to 40 °C
-
Storage Temperature: –25 °C to +55 °C
-
Relative Humidity: 0-95% non-condensing
-
Altitude: Specified for < 1500 m without derating
-
Noise Level: < 65 dB at 1 meter
-
Safety / Compliance / Certifications: IEC/EN 62040-1, IEC/EN 62040-2; RoHS; EMC compliance
Mecer 200kVA ME-200000-GTU II 3/3 Transformerless UPS
-
Rated Capacity: 200 kVA / 180 kW
-
UPS Type: True Online Double-Conversion (transformerless)
-
Phase: 3-Phase input & output (3/3), 3Ph+N+PE
-
Input Voltage: 380 / 400 / 415 VAC nominal
-
Input Voltage Range: ~138-485 VAC at 40% load; ~305-485 VAC at full load
-
Input Power Factor: ≥ 0.99
-
Input THDi (linear load): ≤ 3%
-
Bypass Voltage Range: Configurable ±10%, ±15%, ±20%, or ±25%
-
Output Voltage: 380 / 400 / 415 VAC
-
Voltage Regulation: ±1%
-
Output Power Factor: 0.9
KShs2,300,000
- Prices are subject to change without notice!
- All Prices are VAT Exclusive
Reviews
There are no reviews yet.